Gas heating preventative maintenance performed basement Check filter - Aprilaire 501 electronic core is due ASAP Clean flame sensor Inspect burners - No concerns Ohm test igniter: 59.8 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - 2”pvc no concerns Set thermostat for heat Check amp draw on blower motor: 3.42 Check amp draw on inducer motor:0.79 Check delta T - 59° Furnace is in optimal running conditions Gas heating preventative maintenance performed closet 2nd floor Check filter - 20x25x1 clean Clean flame sensor Inspect burners - clean Ohm test igniter: 54.2 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: Inspect exhaust flu - 2”PVC no concerns Set thermostat for heat Check amp draw on blower motor: 2.92 Check amp draw on inducer motor:0.42 Check delta T - 53° Furnace is in running conditions at this time. 2nd floor system was showing signs of gas valve failure. Un