DCA (dehumidifier corporation of America} Two systems both confirmed refrigerant leaks. System two in the North main front door lobby System one to the south in the main lobby area has visible oil staining on the cooling\dehumidification coil and refrigerant pressures are running very very low. 48 and 143. System is producing an air temperature change from 72.5°f return to 77.1° with a minimal humidity reduction from 63.4% to 57.3%RH. System 2 at the main front doors is not running at all due to 0 PSI of refrigerant R407C After discovering 0 PSI and possible die on the cooling / dehumidifying coil nitrogen pressure confirmed the leak with soap bubbles and video Both systems need air coils replaced The south system is still running with low refrigerant pressure The north system has the power turned off and will not run is it uploading I knew 10 or 15 minutes it might take it Seth will consult with JP and prepare estimates for repair and replacement All equipment in the buildin