Cooling preventative maintenance performed Check filter - 20x25x1 clean Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 35+5 good Check OD fan Amp - 0.64 Check compressor Amp - 5.31 Verify pressures and HP-SC/LP-SH 300/11°\120/14° Delta T - 20° The Air handler and AC are in optimal running conditions.