Furnace had stored ignition failure codes Flame sensor signal was 6.0 micro amps before cleaning Signal rose to 6.7 after cleaning Checked gas pressure, standing inlet was 10.8" Homeowner adjusted regulator to 13" with the furnace operating Manifold pressure 11" Suspect low gas pressure from potentially frozen regulator No issues found with the furnace itself Exhaust pipe is clear