$2,328.15 COD Scheduled with Ted 570-977-2027 Furnish necessary parts and labor to complete the following repairs per manufacture specifications and code requirements: -- Perform minor re-pipe over the fryers to properly aim nozzle protection at the hazard areas -- Install proper nozzle protection over the candy stove -- Install proper protection over the range due to the salamander appliance. The current nozzles are not designed for low proximity protection. This protection will require the nozzles being installed below the salamander. -- Install proper protection over range with back shelf. The current nozzles are not designed for back shelf protection. This protection will require the nozzles being installed below the back shelf. -- Install an additional heat detector over the range, candy stove and fryer due to currently lacking heat detection