Completed spring AC maintenance on a 2-ton Carrier unit. Condenser coil cleaned with foaming cleaner, amp draw on compressor at 8.1A (within range). Capacitor tested 39.6 µF out of 40 µF spec. Refrigerant levels normal. Checked float switch operation and cleaned drain trap. All components functioning as expected for cooling season.