Jacob P.

Jacob P.


Job Checkin

Returned to our clients home to preform another inspection on the finished home. The HVAC system has not changed or been addressed from the previous visits. The system is a 5 ton single stage AC with a 90% furnace for a 3500 sq ft home. The unit is undersized according to the manual J I ran today at the home. I ran the manual J with an average outdoor temperature of 110º and it was closer to 7 tons. There is not enough air being supplied to the entry way of the home. The master bedroom and one of the smaller bedrooms have the return grill within 4 feet of the supply air in the room. There is a large gaps present on the evaporator coil that is allowing a significant amount of air to leak. This is due to a compromised cabinet door that needs to be secured shut. There are several gaps in the return box, a the filter hits the closet door making it inconvenient and difficult to remove and replace. There are several temperature discrepancies between the supply vents in the home some of

Returned to our clients home to preform another inspection on the finished home. The HVAC system has not changed or been addressed from the previous visits. The system is a 5 ton single stage AC with a 90% furnace for a 3500 sq ft home.

The unit is undersized according to the manual J I ran today at the home. I ran the manual J with an average outdoor temperature of 110º and it was closer to 7 tons.

There is not enough air being supplied to the entry way of the home.

The master bedroom and one of the smaller bedrooms have the return grill within 4 feet of the supply air in the room.

There is a large gaps present on the evaporator coil that is allowing a significant amount of air to leak. This is due to a compromised cabinet door that needs to be secured shut.

There are several gaps in the return box, a the filter hits the closet door making it inconvenient and difficult to remove and replace.

There are several temperature discrepancies between the supply vents in the home some of