Performed AC maintenance on a Goodman condenser. Systems temperature split is 20 degrees. Indoor blower motor is heavily caked in dirt. Scroll wheel has hair and dirt on the fins. Filter is dirty and needs changing. Outdoor coils were heavily dirty and chemically washed today. Compressor start amps are high for this setup. Fan amps are in range and components are ok at this time. Refrigerant levels are ok. System was cycled before leaving.