Performed maintenance on a 1996 Lennox gas furnace. Customer reports unbalanced airflow through the house. Frequent use of heater this season. System kicked on ok. The heating temperature split is very high at 71 degrees. This is a cause for concern with a system this age. Sensors and switches were cleaned and tested. Static pressure is high. Combustion blower is in ranges battery cap is ok at this time. Primary blower motor is heavily leaking oil and leaking oil because the Blower wheel is very dirty and rusty. This should be replaced if any number of years is expected moving forward. A safety check was performed with permission. I found the heat exchanger to be very hot, many hot spots and weak spots in numerous areas. This condition was discussed with the homeowner. They want to receive a equipment appointment. System is operational at end of appointment.