Performed diagnostic on 2005 system. Homeowner states that system struggled to cool down the home a couple days ago. It was a rental for 2 years, they are now planning on moving back into the home. Cycled system for cooling. System kicked on normally and started cooling. Checked outdoor unit electrical and system components. Amp draws on compressor are fairly high, and it is not that hot outside currently. Condenser fan motor is fairly close to going over allowed maximum capacity and has started to leak out oil. Secondary motor control is in range and primary motor control is in good condition. Could not check ducting as there is no attic space. System is producing proper temperature split and is cooling correctly. At this time there is not really any repair that the system needs. It is cooling as it should at this time due to it being fresh outside, but based on electrical amp draw compressor is more than likely overheating and shutting off on a hot day, and unit is struggling to keep