520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Job Locations
for bryn mawr, pa


Map of Bryn Mawr PA
Joseph D.

Joseph D.


Job Checkin

Completed 6 Month inspection for 14SEER 1.5 Ton Heat pump. Filter ok (16x20x1) Measured temperature rise (58-78=20°; Outdoor temperature 46°)and static pressure. Inspected wiring and controls: there are no surge protection devices. Left estimate for ZapPro ECM style surge protection for outdoor circuit and Intermatic style surge protector for indoor circuit. Inspected EZ trap and drain. Monitored refrigerant pressures and diagnostics: 80/260 Outdoor temperature 46°; Indoor return air temperature 59° Left estimate for AC+Heat Pump plan membership. Paige May be interested in maintenance plan for the other systems in the building. Many of the systems are approaching replacement age. System is operating well at this time.