AC Tune Up 2 Ton Lennox AC system Made call for cooling from thermostat. Checked 401 Filter:OK. Checked all electric motors and components. Measured refrigerant pressures; measured temperature split. Checked drain. Checked wiring. Checked compressor amps. Found weak blower capacitor. Called Carl who approved replacement of capacitor. Completed AC tune Up Form AC system is operating well at the time of this maintenance.