Found error code E6 Open rollout. Reset. Checked and adjusted propane pressure. Measured static pressure in hi and low fire: Ok Made sure inducer draft was good by verifying with manometer at pressure switch. Allowed system to run appropriately 20 minutes. During this time 0 rollouts occurred. Change auxiliary heat lockout temperature to 35°F at thermostat. Combustion and draft tests: Good