Brennan G Todays visit was for the system not cooling. Preformed inspection and diagnosis and found the thermostat had failed and the outside capacitor was very weak. Replaced both components to get the system up and running. Vacuumed the drain as a courtesy, it backed up while onsite. The current system is out of manufacture warranty and is only a 13 SEER. Also the equipment has multiple concerns regarding cleanliness and reliability. I suggested the equipment be replaced vs repaired. Gave john a replacement estimate. He plans to get other quotes. System is cooling at this time. Service call Replace thermostat (basic Thermostat) Replace compressor fan dual capacitor

Brennan G
Todays visit was for the system not cooling.
Preformed inspection and diagnosis and found the thermostat had failed and the outside capacitor was very weak.
Replaced both components to get the system up and running.
Vacuumed the drain as a courtesy, it backed up while onsite.
The current system is out of manufacture warranty and is only a 13 SEER.
Also the equipment has multiple concerns regarding cleanliness and reliability.
I suggested the equipment be replaced vs repaired.
Gave john a replacement estimate. He plans to get other quotes. 
System is cooling at this time.
Service call 
Replace thermostat (basic Thermostat)
Replace compressor fan dual capacitor