Found system tripping out on high head pressure Removed charge again to still find restriction in 3/8 copper piping at air handler. Removed pipe and repaired with new. Pulled 497 micron vac and checked charge again. System ran for almost 45 mins dropped temp down in home from 80-77 before leaving and pressures never sky rocketed. Believe this is the final fix for this system