Shut up to do a diagnostic on the system went through both systems. First system is a train 2000 1518 zero unit run cap was 39 over4 on the capacitor. It calls for 50 over five that I advise the homeowner that it is weak he is aware of that situation. I would recommend a run cap and a hard start for that system to improve the quality of that machine and it’s life. Second system is a carrier run cap was 27 over4.96 MFD run cap on that system is 30 over five to improve the quality of that machine. I recommend a hard start systems are both operating. I did advise though that run cap once it becomes weak enough it won’t allow the compressor to kick on for the train system. Homeowner is aware gave him five different quotes on Repair repairs versus replaced the system. Homeowner needs to talk to his wife and he’ll get back to us on that end paid 135 for the diagnostic today.