Downstairs system: Performed inspection on 4 ton system. Inspected indoor and outdoor coils, checked temperatures, inspected all major and minor electrical components, checked compressor amps, blower amps, and condenser fan motor amps. This system appears that the compressor was recently replaced and all the biological growth buildup inside the blower cavity Was clean in and around blower, however, the evaporator coil still appears to have some biological growth underneath. The evaporator coil would need to be pulled and cleaned to eliminate all growth buildup. The condenser fan is over amping. Getting 1.25 A while fan is running, the maximum rating is 1.2. That number should be 30 to 40% lower than the maximum reading. The condenser fan motor needs to be replaced. Also, the new compressor has very high startup amps. Getting 125 A on start up and the maximum is supposed to be 117 A. There should’ve been a hard start assist installed with the new compressor so that the amp level would