8999 66th Ct Unit 102
Pinellas Park, FL 33781
727-433-9853

Job Locations
for pinellas park, fl


Map of Pinellas Park FL
Aaron K.

Aaron K.


Job Checkin

Water leaking from air handler, checked drain line, drain is draining fine and is not backed up. Issue was that static pressure is high due to dirty air filter and too thick of air filter. Client is currently using a Merv 11 air filter and should put a Merv five in there to reduce static pressure in the system. Also condenser coil is dirty and condenser fan is over amping. Replaced air filter for client and advised to switch to a lower Merv rated filter. Also client approved to have condenser coil cleaned, however, needs to talk with spouse about any other recommendations made. System is nine years old and recommended replacing due to age and cost of repairs. Period system is running and operating OK at this time.