No cooling, indoor fan and outdoor fan are running, however, the compressor is not. Found bad outdoor capacitor. Also did a complete evaluation on AC system. Could not check refrigerant levels because compressor was not running. Noticed evaporator coil and condenser coil were very dirty, disconnect box plug is passing voltage to condenser when plug is pulled out, contactor is burnt and pitted, and compressor has high startup amps. Gave client solutions for issues with system. Client needs to speak with spouse to approve any recommendations and spouse is not reachable at this time. This is a rental property And they will get back to us by tomorrow if they would like to move forward with any repairs.