No cooling, indoor fan and outdoor fan are running, but the compressor is not. Did a complete evaluation of AC system. Noticed several duct runs in attic leaking air and biological growth buildup around duct connections in air handler. Found blown dual run capacitor outside, which was tied into a second capacitor for the fan as well as hard start kit, which was not working properly. Gave client solutions for issues with system, however, system is 7 years old and recommended replacing ductwork as well as AC system due to age and condition. Client just wanted to do the immediate repair for now. Eliminated the secondary run capacitor and installed a dual run capacitor to take care of the compressor and condenser fan. Replaced hard start assist. Cycled and tested system, all operations OK at this time. Client signed up for monthly membership. Office needs to contact client to schedule first maintenance.