Performed heating maintenance Cleaned flame sensor Found condensate trap gasket leaking water Replaced gasket Blower clean 20x25x1 Filter is good Burners are in new condition High fire gas pressure set to 3.2"wc Temperature rise 53⁰ Low fire gas pressure set to 1.3"wc Temperature rise 46⁰ Furnace is operating within factory specifications at this time