Cooling preventative maintenance performed Check filter - 20x25x4 new today Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 40+5 @ 40.79+5.06 Check OD fan Amp - 0.98 Check compressor Amp - 6.92 Verify pressures and HP-SC/LP-SH Delta T - 20° The Air handler and AC are in optimal running conditions.