Service warranty. Heat pump disconnect was left off. Tested system in heat and cool modes.
2013 Carrier single stage cooling system preventive maintenance inspection, tune up, minor maintenance cleaning, safety inspection, performance inspection. Reinsulate indoor expansion valve sensing bulb and flush drain pan and drain lines to the sump Inspect furnace, ductwork and run test cooling mode at 54.3°f supply air Water flush outdoor HP equipment, run test refrigerant pressures in cooling mode, and inspect All electronics All equipment is running an excellent condition in cooling mode and is clean safe and ready for summer
Water furnace 049 5 series with 1 HP motor Test run package equipment with non-pressurized two pump glycol flow center. Inspect all installation set up and programming at the equipment downstairs and confirm proper setup of the replacement Honeywell t10 thermostat Increase y1 blower speed from five to six and increase y2 blower speed from speed 6 to speed seven G remains on speed 1 and aux remains on speed 10 (default) Damper adjustment in basement for basement supply at the gym corner All mechanicals functions and operations of the package air handler and flow center are within specs. Air flow static pressure is excessive with auxiliary speed 10 at 2250cfm however compressor blower speeds are at the correct & desired CFM range Wes and Jason will follow up with additional duct consultations
Water furnace premiere short cycling on low pressure switch Leak repair at capillary tube joint on suction line Brace over existing joint and pressure test at 65 PSI Evacuate to 500 microns and recharge R22 system running at 53 and 190 in heat mode Minor maintenance shop vac cleaning and drain flush Water furnace premiere 2 second system in the basement, Minor maintenance cleaning, Shop-Vac evaporator coil, run test two-stage heating and thermostat, power flush condensate drain, pressure test ground loop circuit. One two pump flow center and one outdoor ground loop feeds two geothermal systems in the basement ***Auxiliary electric backup heat has broken coils on both air handler systems electric heat was not tested on either piece of equipment homeowner says electric heat is not necessary Homeowner will service washable air filters. no water access due to freezing outdoor conditions today
2014 Carrier GT geothermal three ton non-pressurized two pump glycol. Antifreeze freeze protection is tests between 30 and 35% roughly +5to +10°f freeze protection Electrical diagnostics and repairs Pull new thermostat wire from first floor to basement equipment, confirm correct thermostat setup, trace electrical short to faulty high pressure switch causing equipment to enter limp mode running the compressor, blower fan, and flow center non-stop ”attempting to reset the high pressure switch”. Bypass high pressure switch, research control board dip switch settings. Run test heat pump in low stage and high stage with 87° supply temp and 140° with auxiliary engaged Homeowner understands the water flow restrictions through the DHW heat exchanger and will reroute the 1 in glycol lines ASAP. Running refrigerant pressures under today's conditions are 95 and 300 psi Due to water flow restrictions through the DHW the glycol temperature drop is nearly triple the book specs from 63 to 38
Upon arrival, furnace is showing code for pressure switch did not close or reopened. Hooking up a manometer to the pressure switch that is not closed is showing 0.0inwc of induction. Inducer is running during induction test. Further investigation shows that pressure switch hose is clogged with debris. Performed cleaning to clear out pressure switch hoses and combustion condensation trap. Excessive debris clogging drain trap most likely lead to backing up in the collector box causing pressure switch José to become clogged. Also inspect3d and cleaned flames sensor due to unit being supplied by propane. Flame sensor is in very poor condition with heave corrosion and soon buildup. Flame sensor appears to be corroded in half. Recommended replacing flame sensor ASAP. Hunter found a dir3ct replacement flame sensor on Amazon that he will be taking care himself. Information on propane tank outside. Twist knob on top of tank turns off propane to the house. With knob open to supply the house wi
Phone discussion and estimate for outdoor temperature centers
Install warranty no additional charge Honeywell vision pro 8000 Wi-Fi 8321 has circuitry that is non-compatible with the off/on cycle of the generator. 2 head units and 2 subbases were tested Remove Honeywell vision pro 8000 and install Resideo T10 from truck stock
Install WaterFurnace 5 Series Geothermal system. 2 Stage compressor, Variable Speed ECM blower -Model #NDV049K112CTR0BN Serial: 240801075 Efficiency: Up to 4.8 COP / 28.0 EER Features Included: *Aurora Advanced Controls *15 KW Backup heat *Premium High Static ECM Blower Motor *2 Pump Non Pressurized Flow Center with Connection Kit *2" Merv 11 air filter *GeoLink loop flow center *Honeywell Vision Pro 8000 WiFi thermostat *4 Ton Vertical Loop Field *Aprilaire 700m Humidifier *NuCalgon iWave Air Purifier *Reusable/Washable Electrostatic Air Filter *Hot Water Generation with Storage Tank *Aprilaire E100 Dehumidifier *Ductwork Changes Installation: *Reconnect to existing high voltage electrical circuit *Transition to existing supply and return duct Warranty: (Annual maintenance must be performed) WaterFurnace 10 Year Parts WaterFurnace 5 Year Labor Flow Center and Accessories 5 Year Parts and Labor *** 30% Federal Tax Credit Eligible *** 2% Cash/Check Discount Available **High Voltage
Installed propane conversion kit on a Bryant 2 stage 96% efficient furnace. Wired up the heat pump and thermostat for dual fuel operation.
Waterfurnace geothermal installation near Marengo.