Job Checkin

Instsll warranty Fp1 sensor is reading incorrectly and causing system to trip on fp1 sensor. On site, sensor read 18f while fieldpiece probe read 28f. Will need to get new sensor and return to replace. Called waterfurnace and left voice-mail. Replaced faulty fp1 sensor and test ran system. Verified corrdct reading with temperature probe. System is operational with no errors.