Cooling preventative maintenance performed During cooling maintenance condenser fan motor started off whirring loudly, then after I washed the coil and turned the unit back on the fan motor ran for less than five minutes and seized. Quoted fan motor and quote was approved, picked up and replaced fan motor then finished maintenance. -pulled half the cage to flush debris out of coil full of mulch and pine needles Check filter - 20x25x4 new today Check coil for any buildup or debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD -70mfd @ 68.6 Check OD fan Amp - 2.20 -2.80FLA Check compressor Amp - 6.2- 12.2RLA Verify pressures and SC/SH Delta T - 20° The Air handler and AC are in optimal running conditions.