Performed cooling maintenance Left a 20x25x4 filter Poured treatment down condensate trap Closed humidifier bypass damper Blower is clean Drain is flowing and no signs of leaks Washed Condenser coil Capacitor tested below the 6% tolerance Replaced capacitor Refrigerant charge is correct: 8⁰ subcool, which is the spec Wiring is tight and undamaged System is clean and operating within factory specs at this time