Performed heating maintenance on series 7 waterfurnace geo Upon arrival system heating with compressor speed 12 w/no auxiliary 32⁰ temperature rise (75⁰ return, 107⁰ supply) Inverter current 17A Filter is new, on schedule with homeowner Cleaned inverter drive air filter Water source inlet 56⁰ Water source outlet 48⁰ No active faults Auxiliary heat wiring in good shape, no signs of overheating or corrosion Actual BTU output calculated 61,862 No signs of water leaks inside or outside of the unit Traced open loop plumbing and saw no signs of water leaks All wiring inside the geo is in great shape, found no loose or overheated connections Air coil is in good shape No concerns found on today's visit

Performed heating maintenance on series 7 waterfurnace geo
Upon arrival system heating with compressor speed 12 w/no auxiliary 
32⁰ temperature rise (75⁰ return, 107⁰ supply)
Inverter current 17A
Filter is new, on schedule with homeowner
Cleaned inverter drive air filter
Water source inlet 56⁰
Water source outlet 48⁰
No active faults
Auxiliary heat wiring in good shape, no signs of overheating or corrosion
Actual BTU output calculated 61,862
No signs of water leaks inside or outside of the unit
Traced open loop plumbing and saw no signs of water leaks
All wiring inside the geo is in great shape, found no loose or overheated connections
Air coil is in good shape
No concerns found on today's visit Performed heating maintenance on series 7 waterfurnace geo
Upon arrival system heating with compressor speed 12 w/no auxiliary 
32⁰ temperature rise (75⁰ return, 107⁰ supply)
Inverter current 17A
Filter is new, on schedule with homeowner
Cleaned inverter drive air filter
Water source inlet 56⁰
Water source outlet 48⁰
No active faults
Auxiliary heat wiring in good shape, no signs of overheating or corrosion
Actual BTU output calculated 61,862
No signs of water leaks inside or outside of the unit
Traced open loop plumbing and saw no signs of water leaks
All wiring inside the geo is in great shape, found no loose or overheated connections
Air coil is in good shape
No concerns found on today's visit