Outdoor 90° indoor average 75° Cooling preventative maintenance performed 2nd floor system Check filter - 20x25x4 new today Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Verify pressures and HP-SC/LP-SH 338-11°/130-11° Delta T - 23° The Air handler and AC are in optimal running conditions. Cooling preventative maintenance performed basement zoned Check filter - 20x25x4 new today Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Verify pressures and HP-SC/LP-SH 347-14°/113-10° Delta T - 18° both zones open The Air handler and AC are in optimal running conditions. Cooling preventative maintenance performed basketball court Check filter - 20x25x4 new today Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Verify pressures and HP-SC/LP-SH 340-13°/125