Furnace maintenance inspection performed Inspect filter:20x25x1 clean Inspect burners: Clean no concerns Ohm ignitor: 46 ohms Clean flame sensor Inducer amps: 0.27 Blower Motor amps: 2.20 All wiring OK Humidifier: n/a Temperature rise: 58⁰ propane 30⁰ heat pump Furnace is running in optimum condition.