Graham M.

Graham M.


Job Checkin

Gas heating preventative maintenance performed Check filter - 20x25x1 8/10/25 Clean flame sensor Ohm test igniter: 58.2 Inspect wiring for loose connections and/or hot spots - none found Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 4.2 Check amp draw on inducer motor:0.9 Check delta T - 59° Furnace is in optimal running conditions