Performed heating maintenance Signed up for silver maintenance plan Concern of a no heat condition a few days back where the inducer motor was turning on and off and the house got down to 55⁰ Resetting the power to the furnace solved the issue No fault code history pertaining to a no heat condition Considering that a power reset got the furnace to snap out of what it was doing, suspect a brown out or electric blip from AEP put the system into a confused state Like a computer, rebooting the system clears up a lot of issues that can occur Humidifier water panel was very bad replaced it 20x25x4 filter is in good condition. Still has easily 3 more months of Iife left Repaired a tiny water leak on the inducer outlet, flipping the hose clamp 180⁰ per Daikin service bulletin solves the issue Cleaned flame sensor Blew out Condensate trap Run tested furnace Found humidifier solenoid valve failed: getting 24V to it, it will not open for water flow Quoted a replacement solenoid, wishes to per