Newer filter installed backwards has flattened out and is causing a major air flow blockage. Intialctest run in heating stage 2 showed discharge pressures at 500psi. Installed new air filter and test ran in second stage. Current operation discharge pressures at 350psi and is within spec. Test run operation of humidifier with no issues found.