2001 Trane XB R22 No operation outdoors when thermostat calls for cooling. Contactor engages however breaker in the main panel was in the tripped off position. 440 volt power supply 35 + 4 is below specs causing high amp draws at startup and running Condenser coil is matted over solid on all four sides causing excessively high refrigerant pressures and extra stress on the compressor. Relevel condenser with bricks already on site Water flush condenser coil Reset breaker and run test refrigerant pressures. R22 piston coil is running at 67 with 29 superheat 78ra indoor and 85 outdoors 440 volt power supply is special order. Seth has prepared an estimate and sent for approval