Customer had high humidity and inconsistent cooling. Found blower wheel caked in debris and motor capacitor weak (tested 4.1 µF out of 5 µF). Removed blower assembly, cleaned wheel with degreaser, replaced capacitor, and reset blower speed for high cooling. Post-repair humidity dropped from 68% to 51% indoor RH within 2 hours.