I arrived at our clients home for a a cooling maintenance inspection. Our client had mentioned to me water dripping from the secondary drain line as well as the Unimed having high humidity. I proceeded to visually inspect the attic unit before going outside. Once outside I tested and checked all the electrical components for the system. I also rinsed the outdoor coil from the pet hair and debris that it had collected. Tom was outside and was surprised to see how much hair had collected. Once rinsed off I continued to test the system. I found the contactor to be near failure reading 19.3 Out of 20 ohms. The compressor motor also exceeded manufacture limits. Reaching 128 amps out of 104. I discussed my finding with Tom and went inside to the indoor AirHandler. There I tested the temperature drop and looked into the water that was draining from the secondary pan. I found that the air handler had water collected on the inside cabinet insulation. The water is dripping from here and not t