Arrived at our clients home for a single system cooling maintenance inspection. Our client provided filters to be replaced today. Once I replaced the filter at the indoor attic unit, I proceeded outside to test and inspect the condenser unit. I tested all the electrical components and ensure that they were all testing within manufacturer specifications. I also rinse the outdoor condenser coil as part of today’s maintenance. I then went back into the attic and treated the primary drain line. I measured the temperature coming out of the attic unit and ensured It was cooling with 20° temperature. I did find the indoor blower motor to have dust accumulated on it And subsequently is causing the motor to hive high run amps. The limit is 6.8 and it was currently measuring 4.6. I do recommend a blower wheel cleaning to help reduce the run amps of that motor. Everything else passed inspection today and the unit is cooling properly on departure.