Found system still clogged. I cleared it to the best of my ability last time out, but I discovered that the ptrap was blocked again. I cut and removed the ptrap to fully remove all the build up inside of it. I tested the drain will a half gallon of water and verified that it was clear. The ceiling was wet due to the way the emergency pan is hung. There are screw holes on the front side of the pan. This would cause water to drip out if water levels rise high enough. I adjusted the emergency pan float to right next to the screw hole. This will allow the system to shut off before getting too high to drip. Next step will be full drain reconstruction.