Thermostat only goes up to 70 customer set thermostat to 74 it never reaches 74, customer stated flames would come on but they would go out after minutes of running, found blocked on furnace trap, cleared blockage and test operation, propane as fuel source, secondary heat exchanger collector box is leaking, also needs new burners, also heat exchanger did not passed safety test, ran furnace with out blower for 4 minutes to get steady combustion once blower was energized excess air went up from 115% to 140% carbon monoxide only went up 3 ppm due to condition would recommended replacing furnace