Chris B.

Chris B.


Job Checkin

Diagnosed issues with boiler. Found boiler going off on exceeding water pressure. Airvent was already replaced and verified operational. The previous company left the airvent closed, I also found the limit set at 200F, it factory standard recommended at 180F. Boiler was drained down and the automatic water feeder was tested operational. It maybe passing water through causing access pressure. All base board zones were bled, and the boiler was tested and verified operational. While filling boiler to proper temperature and pressure, there was a slight increase in pressure so I isolated the automatic water feed. The Clint will keep a eye on the water pressure to isolate the expansion tank or the automatic waterfeeder.