Luis T.

Luis T.


Job Checkin

Customer installed ductless system one heat pump and 5 indoor head, upon arrival customer explained they did not pressure test system or evacuate, found almost no refrigerant in the system, quoted to add nitrogen and pressure test system, once we verified no leaks are present then we can move to next step to triple evacuation and re charge, customer ok price, found several connections leaking at the outdoor and 3 indoor head leaking, would recommended reflate all connections and used flare tite, customer will repair all connections, he will call office when he is ready to triple evacuation and re charge unit