Boiler was overfilled. Drain approx 12-15 gallons to get water level to design. Checked over wiring, One big issue has been thermostat location it is in a corner about 10’ up on first floor where there is a breeze from entrance way. The temperature there is 7° cooler than the temperature in any of the apartments themselves. We installed Honeywell S1200 Elite pro thermostat with equipment interface module and a room sensor. Placed the room sensor on a wall in a second floor apartment and configured new thermostat to use this sensor as the temperature input. Set thermostat target 70° Monitored boiler operations. Set auto water feeder delay period to 10 min. Tightened packing nuts on 3 problem radiator valves. They were very lose. There are a couple air vents that need to be replaced. We will provide estimate. System will run alot less often now by virtue of having temperature being read from an actual apartment.

Boiler was overfilled.
Drain approx 12-15 gallons to get water level to design.
Checked over wiring,

One big issue has been thermostat location it is in a corner about 10’ up on first floor where there is a breeze from entrance way. The temperature there is 7° cooler than the temperature in any of the apartments themselves. 
We installed Honeywell S1200 Elite pro thermostat with equipment interface module and a room sensor.  
Placed the room sensor on a wall in a second floor apartment and configured new thermostat to use this sensor as the temperature input.
Set thermostat target 70°
Monitored boiler operations.
Set auto water feeder delay period to 10 min.

Tightened packing nuts on 3 problem radiator valves. They were very lose. 

There are a couple air vents that need to be replaced. We will provide estimate. 

System will run alot less often now by virtue of having temperature being read from an actual apartment. 
Boiler was overfilled.
Drain approx 12-15 gallons to get water level to design.
Checked over wiring,

One big issue has been thermostat location it is in a corner about 10’ up on first floor where there is a breeze from entrance way. The temperature there is 7° cooler than the temperature in any of the apartments themselves. 
We installed Honeywell S1200 Elite pro thermostat with equipment interface module and a room sensor.  
Placed the room sensor on a wall in a second floor apartment and configured new thermostat to use this sensor as the temperature input.
Set thermostat target 70°
Monitored boiler operations.
Set auto water feeder delay period to 10 min.

Tightened packing nuts on 3 problem radiator valves. They were very lose. 

There are a couple air vents that need to be replaced. We will provide estimate. 

System will run alot less often now by virtue of having temperature being read from an actual apartment.