Found oil furnace locked out at the primary control . Hit reset button and oil furnace tried to fire immediately. Oil pump has an oil valve on top and was opening immediately. Found 120 v going to oil valve even when primary control was locked out on reset. Replaced primary control with electronic universal control. Also replaced junked up .85x60 a nozzle and performed combustion test. Oil furnace is working fine at time of service.