Three system office inspection for water on the floor similar to spring 2024 Disassemble, inspect, clean, and flush all three condensate drain traps through to the flooror drain Upon arrival all three systems were set to cooling however only the North Wing and the south wing equipment is functional. The West Wing air handler is on and blowing however no rooftop condenser operation is active. Breaker panel #2 inspection discovered a tripped off 45 amp circuit breaker red flag square d labeled heat pump 2. When breaker was reset the system failed to start the first attempt but did start and continue to run the second attempt producing 53° supply temperature after a few minutes of running time.. Multiple test runs on the roof at the condenser discovered two problems. A shutdown and restart test confirmed a very tightly wound and struggling refrigerant compressor. Multiple off and on testing produced varying results including lock rotor amps at 109 AAC and louder than normal compressor n