Upon arrival, both main breaker panel and internal disconnect breaker were tripped. Turned thermostat off and attempted to reset power. Both breakers go back on with no trips and ther is 208V to the system. First tried to test run fan only, and found that the blower will not kick on. Blower relay clicks and is supplying motor with proper voltage, but no operation. Blower motor has failed and will need replaced. Suspect that blower motor shorted internally leading to breakers tripping and has completely internally failed leading to no breakers tripping even when power is supplied. Quote for blower motor replacement will be made and sent over Friday, January 2nd, sometime in the morning.

Upon arrival, both main breaker panel and internal disconnect breaker were tripped. Turned thermostat off and attempted to reset power. Both breakers go back on with no trips and ther is 208V to the system. First tried to test run fan only, and found that the blower will not kick on. Blower relay clicks and is supplying motor with proper voltage, but no operation. Blower motor has failed and will need replaced. Suspect that blower motor shorted internally leading to breakers tripping and has completely internally failed leading to no breakers tripping even when power is supplied. Quote for blower motor replacement will be made and sent over Friday, January 2nd, sometime in the morning.