System low on refrigerant again. Leak sealant was unable to stop the leak due to the size of the hole. Located UV dye all over the evaporator coil. System out of factory 10 year parts warranty. Replace leaking evaporator coil, pressure test with nitrogen, evacuate, and recharge with R410a refrigerant.