Upon arrival discovered back main unit was not operational. Discovered unit blower motor was extremely hot and producing an awful strong burning smell. Checked capacitor for blower motor and unit was dead 10mfd at 0.0. Replaced capacitor and motor started up with no problem, unit pulling 7.83 amps while blower is operating, unable to see blower amp specs. With motor being under heavy load and overheating like it has, recommending replacement of blower motor for preventative measures. Unit is from 2006 and should be considered for replacement soon if repairs continue to be needed. Two units in the building, both operational at this time but replacement was recommended due to age and part failures on bigger unit.