Furnace not operating upon arrival. DISCOVERED DEFECTIVE indoor blower motor. Motor receiving 120v and capacitor reading 3uf. Tested with mini turbo 5uf and blower motor not engaging. Client would like to have estimate for repairs and replacement for Furnace. System is not operating at departure