Goodman janitrol air conditioner is 26 years old this season and is already known to have a refrigerant leak with leak stop from previous owners and tenants Indoor fan motor turns on and runs however tenant states that sometimes it blows air out of the cold air return. Suspect possible bad fan motor and/or capacitor Fan motor capacitors specs at 7.5, actual reading 6.1 Outdoor system compressor not running with 120 psi r22 refrigerant while off, Dual run capacitor overheated and burned out completely uncompressor terminals and week below specs on fan motor terminal Refrigerant pressures low for the current conditions running at 62 PSI with 48 superheat at 72° Replace 7.5 370 volt indoor fan motor capacitor Replace 5 + 35 370 volt outdoor unit dual run capacitor Recharge 12 oz R422B