Perform cooling PMI Check air filter - 20x25x1 new today gold Add drain pan tablets Shutdown humidifier Check delta T - 18° @ 44° Capacitor MFD - 45+10 @ 44.34+9.49 Compressor Amp - 10.2 Fan Amp - 1.6 Verify refrigerant pressures SH/SC System is operating properly at this time