Cooling preventative maintenance performed Check filter -16x25x1 ok due soon Check coil for any buildup or debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 45+5 @ 43.31+4.99 Check OD fan Amp - 1.21 Check compressor Amp - 17.9 Verify pressures and SC/SH Delta T - 20° The Air handler and AC are in optimal running conditions.